EATON part description

Product Attributes

Material Aluminum
Number of clamping units per pole 12
Heat deflection temperature 100 ˚C
Terminal capacity (single/multi-wire) 3/0 - 5/0 AWG (incoming, fine wire (with sleeve)); 2.5 mm² -35 mm² (outgoing); 14 - 8 AWG (outgoing, fine wire (with sleeve)); 2.5 mm² - 10 mm² (outgoing, fine wire (with sleeve)); 95 mm² - 150 mm² (incoming, fine wire (with sleeve)); 95 mm² - 185 mm² (incoming); 14 - 6 AWG (outgoing); 14 - 8 AWG (outgoing); 3/0 - 350 MCM AWG (incoming); 2.5 mm² - 10 mm² (outgoing); 14 - 6 AWG (outgoing, fine wire (with sleeve)); 2.5 mm² - 16 mm² (outgoing, fine wire (with sleeve)); 2.5 mm² - 25 mm² (outgoing, fine wire (with sleeve)); 2.5 mm² - 16 mm² (outgoing); 14 - 2 AWG (outgoing); 14 - 4 AWG (outgoing, fine wire (with sleeve))
Voltage rating at AC Cu (IEC) - max 1000 VAC
Mounting Method Floor standing distribution board; Surface mounting; Flush mounting
Rated operation current (Ie) Cu (IEC) 300 A
Amperage Rating 400 A
Voltage rating at DC Cu (IEC) - max 1500 VDC
Housing Color Light gray (RAL 7035)
Clamp Material Brass; Nickel plated
DEGREE OF PROTECTION IP10
Conductor cross section (flexible, fine-strand) with cable end sleeve - min 2.5 mm²
Conductor cross section (solid, solid-strand) - min 2.5 mm²
SPECIAL FEATURES Clicks on DIN-rail or on base plate.<br>Save time on wiring.<br>Save 80% on space used.<br>Modular construction, 1-4 pole Systems can be built with several blocks.<br>Material, hexagon socket set screw: Steel<br>This power distribution block is suitable for ALU and CU conductors.<br>Please pay attention to the common handling guidelines when connecting the aluminium conductors.<br>Clean and brush the contact surfaces and lubricate them with an appropriate grease.<br>As precaution the connections should get retightened regularly.<br>Zinc plated (Hexagon socket set screw, Surface finish)
Rated short-time withstand current (Icw) 21 kA
Functions Additional equipment
Housing Material PA66
Number of Poles Single-pole
Flame classification (UL 94) V-0
Conductor cross section (solid, solid-strand) - max 185 mm²
Mounting Position Universal
Comparative tracking index (CTI) 600 V
Conductor cross section (flexible, fine-strand) with cable end sleeve - max 185 mm²
Number of clamp positions per pole 12
Rated peak withstand current 51 kA
Torque Rating 25 Nm / 221.2 lbf (incoming). 2 Nm - 7 Nm / 17 lbf - 62 lbf (outgoing)